Entrainment of air into a balcony spill plume

dc.contributor.authorHarrison, R.
dc.contributor.authorSpearpoint, M.J.
dc.date.accessioned2007-05-24T23:53:55Z
dc.date.available2007-05-24T23:53:55Z
dc.date.issued2006en
dc.description.abstractThis article examines various uncertainties relating to calculation methods for the balcony spill plume. The approach of physical scale modeling is used in the analysis. Comparisons are made between experimental results and predictions made using these calculation methods. This work has demonstrated that the presence of a downstand from the soffit at the spill edge of a compartment opening appears to have little effect on the entrainment of air into the subsequent spill plume. A simplified spill plume formula has also been developed to predict the mass flow rate of gases, which inherently includes entrainment of air into the free endsen
dc.identifier.citationHarrison, R., Spearpoint, M.J. (2006) Entrainment of air into a balcony spill plume. Journal of Fire Protection Engineering, 16(3), pp. 211-245.en
dc.identifier.urihttp://hdl.handle.net/10092/83
dc.language.isoen
dc.publisherUniversity of Canterbury. Civil Engineering.en
dc.rights.urihttps://hdl.handle.net/10092/17651en
dc.subjectbalcony spill plumeen
dc.subjectdownstanden
dc.subjectsmoke ventilationen
dc.subjectentrainmenten
dc.subject.marsdenFields of Research::290000 Engineering and Technology::290800 Civil Engineering::290804 Construction engineeringen
dc.titleEntrainment of air into a balcony spill plumeen
dc.typeJournal Article