Bendre, V.D.Bell, S.Enright, W.Bodger, P.S.2008-09-092008-09-092007Bendre, V.D, Bell, S., Enright, W., Bodger, P.S. (2007) AC High Potential Testing of Large Hydro-Generator Stators Using Open Core Transformers. Ljubljana, Slovenia: 15th International Symposium on High Voltage Engineering (ISH), 27-31 August.http://hdl.handle.net/10092/1537paper T3-303When generator stators are rewound or undergo major repairs, there is often a desire to perform a high potential test. These tests can be completed using d.c., very low frequency or a.c. power frequency test voltages. A.c. power frequency tests are becoming common, but such test are difficult because of the large kVAr requirement to charge the stator insulation capacitance. This is particularly a problem with hydro generator stators because the insulation capacitance is further inflated by physical size. Recently the authors were required to test a stator with just over 1 μF in capacitance to a test voltage of 32 kV, requiring a single-phase controllable high voltage source rated to 286 kVAr prior to considering losses. It is not easy to locate a distribution board to supply this at a power-station site. Resonant circuits are normally applied to complete these tests and minimise the distribution board loadings. In traditional a.c. high potential test sets, large variacs are employed with a high voltage transformer and numerous compensating coils. In this paper an open core transformer is described that can provide high voltage and inductive compensation in an original and most compact manner.enAC High Potential Testing of Large Hydro-Generator Stators Using Open Core TransformersConference Contributions - PublishedFields of Research::290000 Engineering and Technology::290900 Electrical and Electronic Engineering::290901 Electrical engineeringFields of Research::290000 Engineering and Technology::299900 Other Engineering and Technology::299904 Engineering/technology instrumentation